Purpose
This article will guide user how to route the management Ethernet ports to node MMC.
Target Audience
All users who are using Advantech ICVG(CIoT) MIC-5604 uTCA nodes
Steps
The MIC-5604 default NC-SI is routed to the Serdes (Rear) instead of Front IO. Here list the commands to set up NC-SI to front.
- From IPMITool
#ipmitool raw 0x2e 0x40 0x39 0x28 0x00 0x4 0x0 0x0
- From CLI command
# CLI> [b80040392800040000]